Product Information
Technical specifications |
|
Communication | Ethernet |
Power | 9-30V AC/DC |
Mounting and Dimensions | DIN-mounted |
Environment | Protected from weather and wind |
Certifications | CE |
UPS | Optional |
Other | Ethernet cables: Minimum CAT6, shielded in high-interference environments |
Compatible Frequency Meters
Acuvim II
Camille Bauer Aplus
Recommended configuration: Acuvim- IIR- D-5A- P1V3 + AXM WEB2, AXM- DIN
Recommended connection: Modbus TCP
Compatible Power Meters
ABB A43/A44, ABB B23/B24, ADL400N, Carlo Gavazzi EM1xx, Carlo Gavazzi EM24. Eastron SDM630, Elite 440, Schneider EM72xx, Schneider EM6400, Schneider EM6430, Schneider EM6438, Logos, Megacon EMS-96, Lovato DMG, Schneider EM6400NG, Schneider PM2120, Schneider PM2130, Schneider PM2220, Schneider PM2230, Schneider DM6200H, Schneider EM6433H, Schneider EM6436H, Schneider EM6438H, Schneider EM6459H, Schneider PM1120H, Schneider PM1125H, Schneider PM1130H, Schneider PM2105H.
Recommended connection
Modbus TCP
Installation steps
Power Supply
Connect 9-30V AC/DC to ‘power’ input. Note: power over USB will not work.
Network
Connect ethernet port.
See more information in Network section and here: https://www.modio.se/docs/network.
Connection
Modbus TCP - Recommended
Connect the controller on the same local network as the Energy Asset (e.g. Battery system or PV) and Metering.
Modbus RS485 - If Modbus TCP is not supported
Connect the included 3-poled connector to one of ‘Channel 1-3’ on the controller.
Connect the other end to the Modbus connector of the device.
RS485 polarity: A, B and G refers to the labels on the controller.
Note: There is a chance that the installer needs to switch polarity A/B, since the standard of labelling modbus-polarity is inconsistent among manufacturers.